MAGNUM DIGITAL CONTROLLER (MDC) - LIST OF ALARMS
Shutdown and warning fault conditions and the displayed message are described in the following table:
No.
Events
Specification
Protection
Type
Information on
Binary Output
Available
Description
1 AnInIOM Sd SD YES
Shutdown alarm configurable on the input of IG-IOM/
IGS-PTM.
2 AnInIOM Wrn WRN YES
Warning alarm configurable on the input of IG-IOM/
IGS-PTM.
3 Battery Flat SD YES
If the controller switches off during starting sequence
due to bad battery condition, it doesn’t try to start again
and activates this protection.
4 Binary Input CONFIG. YES
Configurable warning/shutdown alarms on the inputs of
IL-NT.
5 ChrgAlternFail WRN YES Failure of the alternator to charge the battery.
6EmergencyStop SD NO
If the input Emergency Stop is opened, shutdown is
immediately activated.
7 Engine Temp Sd SD NO
Water temperature is greater than Sd Water Temp set-
point.
8 Engine Temp Wrn WRN YES
Water temperature is greater than Wrn Water Temp
setpoint.
9 Fgen<, > SD YES
The generator frequency is out of limits given by Gen >f
and Gen <f setpoints.
10 Fuel Level Sd SD YES Fuel level is smaller than Sd Fuel Level setpoint.
11 Fuel Level Wrn WRN YES Fuel level is smaller than Wrn Fuel Level setpoint.
12 GCB fail SD NO Failure of the generator circuit breaker.
13 Igen unbl SD NO The generator current is unbalanced.
14 Low BackupBatt WRN NO RTC backup battery is flat.
15 Oil Press Sd SD NO Oil pressure is smaller than Sd Oil Press setpoint.
16 Oil Press Wrn WRN YES Oil pressure is smaller than Wrn Oil Press setpoint.
17 Overload SD YES
The load is greater than the value given by Overload
setpoint.
18 Overspeed SD YES
The protection comes active if the speed is greater than
Overspeed setpoint.
19 ParamFail NONE NO
Wrong checksum of parameters. Happens typically
after downloading new firmware or changing of the
parameter. The controller stays in INIT mode. Check all
parameters, write at least one new parameter.
20 PickupFault SD NO
Failure of the magnetic pick-up sensor for speed mea-
surement.
21 Sd IOM fail SD NO IOM/IGS-PTM module.
22 SprinkIActive WRN NO The protection is active if the output Sprinkler is closed.
23 Start failed SD YES Gen-set start failed.
24 Stop fail SD YES Gen-set stop failed.
25 Ubat WRN YES
Battery voltage is out of limits given by Batt Undervolt
setpoints.
26 Underspeed SD YES
During starting of the engine, when the rpm reaches the
value of Starting rpm setpoint, the starter is switched off
and the speed of the engine can drop under Start rpm
again. Then the underspeed protection becomes
active. Protection evaluation starts 5 seconds after start
up.