maintenance in red text. A description of the maintenance procedure and the action that will take place when the
timer trips the alarm.
Note: If the measured value is outside the range of a gauge, the needle will not be displayed. The digital value below
the gauge will still show the measured value.
Oil Press: Displays engine oil pressure. Current coolant temperature is displayed directly below the gauge
at all times. The gauge registers oil pressure between 0-100 psi (10-689 kPa). Normal operating pressure
is between 35-80 psi (241-552 kPa).
Coolant Temp: Displays engine coolant temperature. Current coolant temperature is displayed directly
below the gauge at all times. The gauge displays coolant temperature between 150°-250°F (66°-121°C).
Normal operating temperature of the unit is between 180°-200°F (82°-93°C) with an average ambient air
temperature of 70°F (21°C).
Battery: Displays the engine battery voltage. Current battery voltage is displayed directly below the gauge
at all times. The gauge displays battery voltage between 0-50V. A normal reading is 12-14V on 12 volt
systems and 24-26V on 24 volt systems (with the engine running).
ENGINE TAB - MAINTENANCE SCREENS
Additional engine information can be viewed on the Maintenance screens by pressing the left or right arrow and
highlighting the “Engine” tab. Refer to “Maintenance Screens” on page 18 for more information.
DIESEL EXHAUST FILTER MONITORING
This unit is equipped with a Diesel Particulate Filter (DPF) to meet current EPA emissions standards. This section
gives an explanation of the indicators that are displayed on the “DPF Status” screen on the Power Zone™ controller.
Diesel particulate filter information can be found on the “Engine” tab within the Maintenance screens.
To access the DPF Status page, press any direction arrow (“”, “”, “”, “”) to enter the Maintenance screens,
and then press the “” directional arrow on the “Engine” tab to toggle through pages until the “DPF Status” page
appears. There are four areas on the “DPF Status” screen that communicate various information to the operator.
The areas and indicators that appear in those areas are explained here:
HEST Lamp (High Exhaust System Temperature): This area will display the Regeneration Underway
indicator above the words “HEST Lamp - Solid” when the unit is in the process of diesel exhaust filter
regeneration. During the regeneration process, the exhaust temperature will be very high.
DPF Lamp: This area will display the Regeneration indicator above the words “DPF Lamp - Solid” when
auto exhaust filter cleaning is enabled. When the unit is being operated with auto exhaust filter cleaning
disabled, the indicator will begin to flash above the words “DPF Lamp -Flashing” if the soot load level goes
above 80%.