CARBON MONOXIDE: USING A GENERATOR INDOORS CAN KILL YOU IN MINUTES.
2. The main display will show the prestart diagnosis and the controller will load the unit management software.
3. When the software is loaded, the Home screen will be displayed and the controller will be in “Manual Mode” as
indicated at the top of the screen.
Note: The controller can be started from any screen when it is in “Manual Mode.”
4. Press the green Engine Start “I” button on the controller. The controller will initiate the startup procedure and
start the engine, provided there are no engine faults preventing the unit from starting.
Note: It may take a few seconds for the engine to run smoothly and reach its governed operating speed. During this
time, the display will show a voltage different from that set with the voltage selector switch.
5. If the engine does not start after the first cranking attempt, the engine will pause for 15 seconds to allow the
starter to cool. The main display will show “Manual Mode - Crank Rest.” The engine will make two more attempts
to start for a total of three crank cycles.
6. Should the engine not start and run within three starting cycles, the main display will show the “Fail to Start”
alarm. The starting sequence may be repeated after the starter has had a minimum of two minutes to cool. Press
the Enter “” button to clear the alarm and reset the controller.
Note: The engine controller may skip the preheat engine steps on some of the larger models.